Lỗi the connection for tag is not available s7 1200 năm 2024

Looks like the tag table isn't set up right. On your second post, if you click the box with the three dots next to the tag box, you can assign a PLC tag to the HMI directly. This will add the tag to your HMI tag table and sort out the connections.

You can also add tags in bulk by just highlighting everything you want from the PLC tag table and copy/paste to the HMI tag table.

  • 5

Your 'PLC' connection is in pink because it doesn't recognise it. Your actual plc name in your project is 'PLC_1'.

In the project tree go to the connections just below the HMI tags and set the connection correctly.

You will probably then need to set that connection to your tags where the pink bit is.

  • 6

    Your 'PLC' connection is in pink because it doesn't recognise it. Your actual plc name in your project is 'PLC_1'.

In the project tree go to the connections just below the HMI tags and set the connection correctly.

You will probably then need to set that connection to your tags where the pink bit is.

Thanks for this. This is what is on the Connections...

Lỗi the connection for tag is not available s7 1200 năm 2024

  • 7

Hmm, now PLC_1 is not recognised (?) Clearly, there's something basic I've not done - not uncommon for me!

Lỗi the connection for tag is not available s7 1200 năm 2024

  • 8

Go to connections, delete PLC, then add new and enter the correct addresses for your setup. In your current PLC connection there is nothing in the partner or node columns so it doesnt know what its trying to connect to.

Actually, just a thought. Highlight the PLC connection, then in the parameter section below see if you have the correct ip adresses and interface set as ethernet and access point as S7online

  • 9

    Actually, just a thought. Highlight the PLC connection, then in the parameter section below see if you have the correct ip adresses and interface set as ethernet and access point as S7online

Here's what I've got, bb76.

Lỗi the connection for tag is not available s7 1200 năm 2024

  • 10

Try adding a new hmi and it should pop up and ask you if you want to create a connection to a plc in the priject and create that automatically. You can the copy and paste your screens over and delete the original one

  • 11

    Try adding a new hmi and it should pop up and ask you if you want to create a connection to a plc in the priject and create that automatically. You can the copy and paste your screens over and delete the original one

I did that, thanks,...it's looking a bit healthier because the station/node/partner fields are filled in...